AutoLearn™ line leak detection
Line Leak Detection System
AutoLearn™ line leak detection
Line Leak Detection System
The TS-LS300 AutoLearn™ line leak detection system learns the exact characteristics of each line, ensuring unparalleled accuracy. It can run independently or with any TS-1001, TS-2001 or TS-508 tank gauge.
- Automatically learns exact pipeline characteristics.
- No pipe type and length programming required.
- Monitors flexible, steel and/or fiberglass pipelines in any combination up to certified maximum values.
- Works with submersible pumps generating 25 psi or more.
- Automatically performs 3.0 gph, 0.2 gph and 0.1 gph line tests.
- Positive submersible pump shutdown in the event of a leak.
- Can be monitored through ATG and System Sentinel™.
- Third party certified for 0% probability of false alarm.
- Eliminates the need for factory calibration or on-site field judgments for set-up.
- For use in rigid, flex and rigid/flex piping configuration.
- Immediate notification of alarm condition.
- Allows printed compliance reports.
Console Specifications
- Number of lines monitored: 1, 2, 3 or 4.
- Dimensions: 11" × 12" × 4".
- Power requirements:
- 115 VAC - +15%, -10%, 100 Watts maximum, 1 Amp maximum.
- 230 VAC - +15%, -10%, 100 Watts maximum, 0.5 Amp maximum.
- Operating temperature: 20° to 122 °F (10° to 50 °C).
Leak Sensing Transducer Specifications
- Number of lines monitored: 1.
- Dimensions: 6-1/4" × 2" NPT.
- Applicable liquids: motor fuels.
- Power requirements:
- 10 to 20 VDC from console.
- Operating temperature: -40° to 149 °F (-40° to 66 °C).
- Operating pressure: 0 to 100 psi (0 to 689 kPa).
- Belden™ cable: #9363-22 AWG, #9364-20 AWG or #9365-18 AWG.
- Max. sensor to console cable distance:
- 500' (152.4 M).
- Sensor port fitting: 2" female NPT.
- Sensor material: anodized aluminum body and stainless steel sensor.
- Intrinsic safety rating: Class 1, Div. 1, Group D, II (1) G [EEX la] IIA T4
Capabilities
- The TS-LS300 performs a 3.0 gph leak and pressure test after every dispense. Upon detection of a failed test, the LS300 will alarm and positively shutdown the affected turbine.
- The TS-LS300 continuously monitors pressurized lines for thermally stable conditions and performs a 0.2 gph monthly and 0.1 gph annual precision leak test during the thermally stable union.
- AutoLearn™ line leak detection technology is also available with the TS-LS500, part of the EVO™ Series 550 and EVO™ Series 5000 fuel management systems.
Approvals/Certifications
- UL
- Third party certification of leak detection capabilities
Catalogs
FFS-0216 (UL) FFS Product Catalog.pdf | 62.19 MB |